C.A 6547 CHAUVIN ARNOUX
Виробник: CHAUVIN ARNOUXCategory: Insulation Resistance Meters
Description: Meter: insulation resistance; LCD; VAC: 1÷5100V; VDC: 1÷5100V; IP53
Type of meter: insulation resistance
Kind of display used: LCD
Body dimensions: 270x250x180mm
Weight without batteries: 4.3kg
Power supply: rechargeable battery Ni-MH x1
Measuring instrument features: polarization index (PI), dielelectric absorption ratio (DAR) and dielectric discharge (DD); settable MIN/MAX alarm thresholds
Standard equipment: 1 lead with rear connection 0,35m length; carrying case; mains cable; test leads with crocodile clips; USB cable; user's manual
Measurement: AC voltage; capacitance; DC voltage; dielectric absorption ratio (DAR); insulation resistance; leakage current
IP rating: IP53
Interface: USB
Illumination: yes
DC voltage measuring range: 1...5100V
AC voltage measuring range: 1...5100V
Capacitance measuring range: 1mF...49.99F
DC voltage measuring accuracy: ±(5% + 3 digit)
Insulation resistance measuring accuracy: ±(5% + 3digit)
Test voltage: 40...5100V; 500V; 1kV; 2.5kV; 5kV
Supply voltage: 85...265V AC
Insulation resistance measuring ranges: 10kΩ...2TΩ; 10kΩ...4TΩ; 10kΩ...10TΩ
Conform to the norm: CAT I 2500V; CAT III 1000V; EN 61010; EN 61557
товару немає в наявності
Відгуки про товар
Написати відгук
Технічний опис C.A 6547 CHAUVIN ARNOUX
Category: Insulation Resistance Meters, Description: Meter: insulation resistance; LCD; VAC: 1÷5100V; VDC: 1÷5100V; IP53, Type of meter: insulation resistance, Kind of display used: LCD, Body dimensions: 270x250x180mm, Weight without batteries: 4.3kg, Power supply: rechargeable battery Ni-MH x1, Measuring instrument features: polarization index (PI), dielelectric absorption ratio (DAR) and dielectric discharge (DD); settable MIN/MAX alarm thresholds, Standard equipment: 1 lead with rear connection 0,35m length; carrying case; mains cable; test leads with crocodile clips; USB cable; user's manual, Measurement: AC voltage; capacitance; DC voltage; dielectric absorption ratio (DAR); insulation resistance; leakage current, IP rating: IP53, Interface: USB, Illumination: yes, DC voltage measuring range: 1...5100V, AC voltage measuring range: 1...5100V, Capacitance measuring range: 1mF...49.99F, DC voltage measuring accuracy: ±(5% + 3 digit), Insulation resistance measuring accuracy: ±(5% + 3digit), Test voltage: 40...5100V; 500V; 1kV; 2.5kV; 5kV, Supply voltage: 85...265V AC, Insulation resistance measuring ranges: 10kΩ...2TΩ; 10kΩ...4TΩ; 10kΩ...10TΩ, Conform to the norm: CAT I 2500V; CAT III 1000V; EN 61010; EN 61557.